Free tool · Hydronic
Mixing valve calculator
Size a 2-way injection mixing valve for a radiant or low-temperature loop from three numbers: the loop's design load, the boiler supply temperature, and the mixed return.
Direct answer
Injection GPM = load ÷ (500 × (Ti − Tr)) for water (Taco Eq. 1). 40,000 BTU/hr with 180°F supply and 100°F return is 1.0 GPM. Pick the Taco iSeries 2-way body whose published Cv is closest to that GPM — not the one that matches the pipe size.
Inputs
Taco Eq. 1 — load, boiler supply (Ti), mixed return (Tr).
60 min/hr x 8.33 lb/gal x 1.0 BTU/lb-F. The constant Taco uses in Eq. 1.
How it was picked
The judgment call
An injection valve moves only the hot water that crosses into the mixed loop, so the flows are small — often one or two GPM for a whole radiant zone. That is why Taco tells you not to size the 2-way body from pipe size: a 1" valve on a 1" line with 1 GPM through it has almost no authority and hunts. The wider the Ti − Tr gap, the smaller the injection flow and the smaller the valve.
Note the printed Cv table is not monotonic (3/4" is 10.3, 1" is 8.9); this tool reproduces it as published. For 3-way and 4-way bodies, step size, pressure drop, and glycol corrections, use the full injection mixing calculator and the GPM → Cv guide. Setting the reset curve that drives the valve: outdoor reset calculator.
Estimate only
FAQ
How do you size a mixing valve for radiant heat?
Compute the design injection flow: GPM = load ÷ (500 × (boiler supply − mixed return)) for water. Then choose the Taco iSeries 2-way body whose published Cv is closest to that GPM (Taco PA04/PA06 step 5).
Should the mixing valve match the pipe size?
No. Taco states not to size the 2-way iSeries valve based solely on pipe size. Injection flows are small, so the right body is often smaller than the line.
What constant do I use for glycol?
Water uses 500 (60 × 8.33 × 1.0). Common rules of thumb are about 490 for 30% propylene glycol and 450 for 50%; verify with the glycol manufacturer’s specific heat and density.
What are the Taco iSeries 2-way Cv values?
As published: 1/2" Cv 4.9, 3/4" Cv 10.3, 1" Cv 8.9 (Taco PA04 / PA06).