Field guide · Radiator vents
Hoffman 1A vs Gorton C: CFM compared
“Hoffman 1A or Gorton C?” usually means one upstairs radiator is last to heat and someone says put a C on it. That is usually the right direction — but only after the mains are proven, and only if the room is not the one the thermostat lives in.
Direct answer
Gorton C ≈ 1.9× a Hoffman 1A. 1A at max (setting 6) = 0.145 / 0.225 / 0.300 CFM; Gorton C = 0.27 / 0.45 / 0.57 CFM at 1 / 2 / 3 oz (Gill & Pajek). A 1A on 6 ≈ a Gorton #6 — no dial left. Mains vented, rad still late? Swap to C; never on the thermostat radiator.
Estimate only
What the question usually means
A slow far radiator, an adjustable vent, and advice from the counter.
The Hoffman 1A is an adjustable radiator vent: a dial from 1 to 6 changes the orifice, so the same valve can be slow or (relatively) quick. On a one-pipe job it is the most common thing already hanging on the radiator when someone starts chasing a cold room.
“Hoffman 1A vs Gorton C” is therefore rarely a shopping question. It is “my upstairs rad is late — is a C actually faster than what is on there now?” The honest answer needs three things: the published capacity of both valves, proof the mains are not the real bottleneck, and the EDR plus runout volume that sets the required rate.
Published capacity — the only numbers that matter
CFM at boiler pressure, as measured and published.
| Vent | 1 oz | 2 oz | 3 oz | Orifice |
|---|---|---|---|---|
| Hoffman 1A (setting 6, max) | 0.145 | 0.225 | 0.300 | Adjustable; figures are the maximum setting |
| Gorton #6 | 0.150 | 0.235 | 0.300 | Fixed orifice |
| Gorton C | 0.270 | 0.450 | 0.570 | Fixed orifice |
| Gorton D | 0.330 | 0.540 | 0.700 | Fixed orifice |
Read the table as a ladder, not a verdict. A 1A wide open lands essentially on top of a Gorton #6 (0.150 / 0.235 / 0.300) — which is exactly why opening the dial further does nothing once it is already at 6. Gorton C is the next real step: about 1.9× the 1A at the 1 oz column, 2.0× at 2 oz.
Only setting 6 is listed. Intermediate 1A settings are not published here, and interpolating an adjustable's dial positions into CFM would be an invented number — if the dial is not at max, the honest statement is “less than 0.145 CFM at 1 oz.”
Decision tree
Work it in this order or you will buy the wrong vent.
- Is the vent dead, clogged, or the pitch wrong? A vent that has failed shut passes nothing, and no letter on the box fixes that. A radiator pitched back toward the valve holds water and spits. Rule both out before you spend money — a stuck 1A masquerades as an undersized 1A every winter.
- Are the main vents undersized? Until the main is clear, every radiator on it is waiting for air that has nowhere to go, and the far end waits longest. This is the single most common reason one upstairs radiator “needs a bigger vent.” Size the mains in the main vent sizer and check the count against how many Gorton #2s you actually need.
- Only then, size the orifice. Required CFM = (radiator + runout cu ft) ÷ target minutes. Pick the smallest published vent that meets that rate at your ounce column, then step up for geography if the room is far or cold. A 1A already at 6 that still misses the rate is the textbook case for a C.
When NOT to jump straight to a D
Gorton D is 0.33 / 0.54 / 0.70 CFM — faster than C, and Gorton places it “where a large amount of air must be vented.” That is a specific condition, not a default. Skip the D when:
- C already meets the required rate. Buying extra capacity you do not need just moves the imbalance to a different room.
- The mains are still the bottleneck. A D on a starved main is a louder version of the same problem — and fast venting into a wet main invites hammer.
- It is the thermostat's room. Never. That radiator is the building's sensor; fill it first and the boiler shuts down while the rest of the house is still cold.
Noise is the other tell. A big orifice on a rad that does not need it whistles and spits more than a correctly sized one, and the complaint call costs more than the vent.
Do not oversize the thermostat radiator
How to verify the swap
Time it, do not guess. Before you touch anything, fire the boiler from cold and write down the order in which radiators start to heat, plus the clock time the late one goes hot end to end. That baseline is what tells you whether the new vent did anything.
After the swap, fire from cold again and repeat. A 1A at 6 replaced by a C should visibly move the late radiator up the order. If it does not, the restriction is upstream — go back to the main vents, the supply valve, or the pitch. Two radiators that now race each other mean you moved the imbalance rather than fixing it; step the newly-fast one back down.
Next step
Put the late radiator's EDR, construction, runout, ounce column, and target minutes into the sizer. If the required CFM lands above the 1A's published max, the C is the next rung — and the calculator will say so from the cited table.
Open radiator vent sizerRelated: Gorton C or D · Don't oversize the thermostat vent · How many Gorton #2 main vents · All guides
FAQ
How much faster is a Gorton C than a Hoffman 1A?
Yes — about 1.9× at 1 oz and 2.0× at 2 oz. Gill & Pajek: Hoffman 1A at setting 6 = 0.145 / 0.225 / 0.300 CFM; Gorton C = 0.270 / 0.450 / 0.570 CFM at 1 / 2 / 3 oz. A 1A at max is already near a Gorton #6 (0.150 / 0.235 / 0.300), so opening the dial further gains nothing once it is at 6.
Should I replace every Hoffman 1A with a Gorton C?
No. Size each radiator from EDR plus runout volume divided by your target minutes, and pick the smallest published vent that meets the rate. Fix undersized main vents first, and keep the thermostat-room radiator deliberately small — a blanket C swap usually just moves the imbalance to a new room.
When do I need a Gorton D instead of a C?
Only when the required CFM exceeds C at your ounce column, or geography calls for a large air dump on a far/cold radiator. D is 0.330 / 0.540 / 0.700 CFM at 1 / 2 / 3 oz. Never put one on the thermostat radiator, and do not use a D to paper over starved mains.
Mains or radiator vents first?
Mains first. A late upstairs radiator is far more often an undersized end-of-main vent than an undersized radiator vent — until the main is clear, everything on it is waiting for air that has nowhere to go. Size the mains in the main vent sizer, then tune radiator orifices.
Can I just open the Hoffman 1A up more?
Only if it is not already at 6. Setting 6 is the maximum and is still a modest 0.145 CFM at 1 oz — about the same as a Gorton #6. If the dial is at max, the mains check out, and the radiator is still late, a fixed Gorton C is the usual next step.
Sources
Every CFM figure on this page — Hoffman 1A setting 6 and the Gorton letters alike — is transcribed from the RADIATOR VENTS table of the Gill & Pajek capacity chart. Placement wording (“farthest from the boiler,” “where a large amount of air must be vented”) is Gorton's own. No capacity here is interpolated, and intermediate 1A dial settings are deliberately not given a number.